GUIDELINES

Service Size Cable Size Connection Type
50Amp 8/4 Type W CS8725 CS6365
60-90Amp 6/4 Type W S15 Cam
100Amp 4/4 Type W S15 Cam
150Amp 2/4 Type W or #4 Type W individual S15 Cam
175Amp #2 Type W individual S16 Cam
200Amp  #2 Type W individual S16 Cam

 

FAIR STANDARD EQUIPMENT

Voltage may vary depending on location 120/240V or 120/208V
Outlet description 20A 120V GFCI, 30A 120V TT-30R, 50A 240V 14-50R, 100A 240V fused disconnect